Specification of Wall mount Home UPS  |Pure Sinewave UPS|HU Series (Sine wave)

Specification of Wall mount Home UPS


6 / 8 / 10 KVA

Code HU_KVA2

CTR 2550





Features:                                  

 

Un-limited load applicability.          

Un-limited batteries backup time.           

Parameter Pre-settable.        

DC start and automatic self-diagnostic function.             

Optional Multiple interfaces cards available.           

Compatible with both linear & non-linear load.        

Support solar panel.              

24 hours operation on the inverter.         

High efficiency design to save electricity.               

Controllable & Removable panel with LCD.           

Low DC Voltage supports Office and Home appliances.         

Low heat dissipation in long time operation.            

Multi-stage charger supports batteries up to 600AH.               

Designed to operate under harsh environment.        

 

Model

 Mode

HU-6.0K

HU-8.0K

HU-10.0K

 

Capacity

VA / Watt

6.0KVA / 3900W

8.0KVA / 6.4KW

10.0KVA / 8.0KW

 

 Input

 Nominal Voltage

 230Vac / 120Vac

   230Vac(only)

 

 Voltage Range

 Acceptable Voltage Range

 120Vac-270Vac / 60Vac-135Vac

 120Vac-270Vac

 

 Frequency

 

 

 Line Low Transfer

 120Vac ± 2% ; 60Vac ± 2%

 120Vac ± 2%

 

 Line Low Return

 130Vac ± 2% ; 65Vac ± 2%

 130Vac ± 2%

 

 Line High Transfer

 270Vac ± 2% ; 135Vac ± 2%

 270Vac ± 2%

 

 Line High Return

 260Vac ± 2% ; 130Vac ± 2%

 260Vac ± 2%

 

 Output

 Voltage

 230Vac (220V or 240Vac re-settable via LCD panel);
120Vac (110V or 115Vac re-settable via LCD panel)

 

 Voltage Regulation

 Line Mode

 Follow Ac Line Voltage

 

 Battery Mode

 < 3% RMS for entire battery voltage range

 

 Frequency Regulation

 Line Mode

 Follow Ac Line Hz

 

 Battery Mode

 50Hz or 60Hz  ±0.1Hz

 

 Waveform

 Pure Sinewave

 

Power Factor

 0.65

 0.8

 

Effiecincy

 > 80%

 

Overload Protection

 Line Mode

 Circuit Breaker

 

 Battery Mode

 110% ~ 150% for 30 sec. , >150% for 200ms

 

Transfer Time

Typical

 < 8 ms.

 

 Battery

 Battery Voltage

24Vdc

48Vdc

 

 Backup Time(at Full Load)

Long Time Available

 

 Max. Charging Current
(5 Steps Selectable)

> 60.0A

 

Display  for LCD(Option)

LCD

UPS status, I/P&O/P Voltage Frequency, Load%,
Battery Voltage & %, Temperature, Model

 
 

LED

Normal (Green), Warning (Yellow), Fault (Red)

 

Remote Panel(Option)

 

 

 
 

 Audible Alarm

Battery  Mode

      Beeping every 4 seconds

 

Low Battery

Beeping every second

 

UPS Fault

Beeping Continuously

 

Overload

      Beeping twice per second

 

 Environment

 Operation Temperature

0-40 degree C; 32-104 degree F

 

 Relative Humidity

0-95% non-dondensing

 

 Audible Noise

Less than 45dBA (at 1M)

 

 Physical

 Net Weigh (Kgs)

 49.2Kg

 51.4Kg

55Kg

 

 Dimension(WxHxD)mm

355 x 600 x 260

355 x 600 x 260

355 x 600 x 260

 

 * Specifications are subjected to change without prior notice.

 

 

 


Add to inquiry

Faded Short Sleeve T-shirts

Specification of Wall mount Home UPS

6 / 8 / 10 KVA